image



 


TYPE Pin type
Number of CT  3CT
Overcurrent protection *
Phase loss protection *
Locked rotor protection *
Unbalance protection *
Phase inversion protection * (3PR)
Current setting range  (Α) 1 ~ 5
4.4 ~ 22
Power supply voltage AC 100 ~ 260V
Frequency 50/60Hz
Trip indicator Red/Green
LED
Dimensions (mm) W x H x D 53 x 77.5 x 87.5
Mounting Directly on GMC relays
Applied MC GMC-9, GMC-12, GMC-18, GMC-22
Certifications UL, CUL, CE

PROTECTION FUNCTIONS
Overcurrent:
In conjunction with typical inverse time curve.

Phase loss:
Circuit trips within 3sec when there is a loss of phase of more than 70%.

Note:
In 2CT relays, protection is only offered in 2 phases.

Locked rotor:
In conjunction with typical inverse time curve.

Phase unbalance:
Within 5sec for a loss of phase of more than 50%.

Phase inversion:
Within 1sec.

Dimensions:

alt


Certificates:  RoHS ,  ISO 9001 ,  ISO 14001 ,  ISO 18001