TYPE
|
Screw type
|
Number of CT
|
2CT
|
Overcurrent protection
|
*
|
Phase loss protection
|
*
|
Locked rotor protection
|
*
|
Unbalance protection
|
-
|
Phase inversion protection
|
-
|
Current setting range (Α)
|
16 ~ 80
|
Power supply voltage
|
AC 100 ~ 260V
|
Frequency
|
50/60Hz
|
Trip indicator
|
Red LED
|
Dimensions (mm) W x H x D
|
89 x 77.5 x 94.4
|
Mounting
|
Direct/ Separate (screw or Din rail)
|
Applied MC
|
GMC-50, 65, 75, 85
|
Certifications
|
UL, CUL, CE
|
PROTECTION FUNCTIONS
Overcurrent:
In conjunction with typical inverse time curve.
Phase loss:
Circuit trips within 3sec when there is a loss of phase of more than 70%.
Note:
In 2CT relays, protection is only offered in 2 phases.
Locked rotor:
In conjunction with typical inverse time curve.
Phase unbalance:
Within 5sec for a loss of phase of more than 50%.
Phase inversion:
Within 1sec.