TYPE |
Pin type |
Number of CT |
3CT |
Overcurrent protection |
* |
Phase loss protection |
* |
Locked rotor protection |
* |
Unbalance protection |
* |
Phase inversion protection |
* (3PR) |
Current setting range (Α) |
1 ~ 5
4.4 ~ 22 |
Power supply voltage |
AC 100 ~ 260V |
Frequency |
50/60Hz |
Trip indicator |
Red/Green
LED |
Dimensions (mm) W x H x D |
53 x 77.5 x 87.5 |
Mounting |
Directly on GMC relays |
Applied MC |
GMC-9, GMC-12, GMC-18, GMC-22 |
Certifications |
UL, CUL, CE |
PROTECTION FUNCTIONS
Overcurrent:
In conjunction with typical inverse time curve.
Phase loss:
Circuit trips within 3sec when there is a loss of phase of more than 70%.
Note:
In 2CT relays, protection is only offered in 2 phases.
Locked rotor:
In conjunction with typical inverse time curve.
Phase unbalance:
Within 5sec for a loss of phase of more than 50%.
Phase inversion:
Within 1sec.
Dimensions:
Certificates: RoHS , ISO 9001 , ISO 14001 , ISO 18001